Introduction to MI Cable

Introduction to MI Cable

2023-08-22

Mineral insulated cable is named for what is inside it. In place of a polymer, the space between the conductors and the outer sheath is filled with a compacted mineral, magnesium oxide, and the outer sheath is a drawn metal tube. The name describes the construction, and nearly every property the cable is bought for follows from that one difference.

Cross-sections of mineral insulated cable showing the metal sheath, the compacted mineral insulation and the conductor cores in single-core and multi-core constructions

What the Name Says

Three words carry three decisions, and a fourth term that is often attached to the name means something else.

Term What it says What it does not say
Mineral The insulation is a mineral, magnesium oxide, compacted into the space around the conductors It does not promise the flexibility of a polymer-insulated cable
Insulated The conductors are separated from the sheath by that mineral along the whole length It does not state the temperature the cable will survive, which the materials decide
Cable It carries a signal or a current, and it is supplied in lengths It does not mean power circuits are the only duty it is made for
"Armored", where the term is attached The metal sheath sits outside the insulation and takes the mechanical load It does not describe a separate armour layer, because the metal sheath is already the outer layer

The distinction matters when a specification is written, because two of those terms are used loosely on catalogue pages for the same product, and a buyer who reads "armored" as a second layer will expect a construction the cable does not have.

The Three Parts, and the Line Each One Decides

The construction has three parts. Each is chosen separately, and each is written on a different line of the order.

Part Material options The line it decides
Sheath SS304, SS316, SS321 or Incoloy 800 The temperature ceiling, and the resistance to whatever is in the atmosphere at the measuring point
Insulation Compacted magnesium oxide Nothing the buyer chooses. It is the reason the cable is inorganic, and therefore the reason for the fire and moisture behaviour
Conductor Thermocouple alloys for Types K, J, T, N, E, S and B, copper, or a nickel-chromium resistance alloy The signal the instrument reads, or the current the circuit carries

Because the sheath and the insulator are both inorganic, the cable holds its circuit through a fire without an added fire-rated layer, and it does not depend on a jacket staying intact to keep moisture away from the conductor. The metal sheath does a second job at the same time: it screens the millivolt signal a thermocouple produces from the electrical noise of the plant around it.

How a Designation Is Read

An MI cable is specified in one short line, and the line works differently depending on the duty. On a thermocouple cable the size given is the sheath outside diameter; on a power or heating cable the number is the conductor cross-section. Reading one as the other is the most common mistake made from a catalogue page.

Field Thermocouple cable Power or heating cable
Conductor The type, with both legs identified: for example a Type T pair is written TP and TN, and a Type N pair NP and NN Copper, or a nickel-chromium resistance alloy
Sheath SS304, SS316, SS321 or Incoloy 800 Copper or stainless, depending on the circuit
Size The sheath outside diameter: 0.5 mm, 1.5 mm, 3.2 mm or 12.7 mm The conductor cross-section, written as cores by area, for example 4 x 70 mm
Cores One or two Two and above

A typical thermocouple line therefore reads as a type, a sheath and a diameter together, such as a Type J pair in a 3.2 mm SS321 sheath, or a single-core Type K pair in a stainless sheath. The diameter is doing two jobs at once: a narrower sheath reacts faster to a change at the tip, and a wider one survives more mechanical abuse before the insulation is reached.

The two legs of a pair are written separately because they are different alloys. A cable ordered with the legs the wrong way round reverses the polarity at the instrument, and the reading arrives inverted, which is a fault that looks like a calibration problem and is not one.

MI Cable Against the Alternatives

Three other constructions do part of the same work, and the choice between them turns on the installation as much as on the temperature.

Option Where it wins Where it loses
Mineral insulated cable Fire, heat, moisture and mechanical abuse, with a signal or a supply carried through the same run A larger bend radius than a flexible cable, and an end that has to be terminated properly to stay dry
Fire-rated polymer cable Cheaper over long runs, and it routes like an ordinary cable The fire performance comes from added layers and has to be demonstrated by test; it is still an organic construction, with the temperature limits that follow
Sheathed thermocouple assembly A finished measuring point that arrives with its fittings and head ready to install Built around one point, and less easy to adapt on site
PTFE or glass-insulated thermocouple wire Light, inexpensive, and quick to route inside a panel Not for the hot end, and no protection against mechanical damage

None of the four is better in general. Each is the answer to a different installation question, and the metal-sheathed cable is the one to reach for when the run has to keep working while everything around it does not.

What MI Cable Does Not Do

Four limits are worth knowing before the cable is ordered, because each one is cheaper to design around than to correct on site.

Limit Why What to do about it
It does not bend to a tight radius The sheath is a drawn metal tube and the insulation is compacted powder, so the construction has a minimum bend radius Plan the route with that radius, and order the length the run needs
It does not tolerate a breached sheath Magnesium oxide is hygroscopic, so an open or damaged end takes up moisture and the insulation resistance falls Keep the ends sealed until the cable is terminated, and inspect the sheath before it is installed
It does not repair a measuring point The cable carries the signal; it cannot correct an immersion depth or a location that is wrong Set the diameter from the response time the loop needs, and the tip position from the process
The sheath sets an atmosphere limit, not only a temperature Sulfur attacks nickel-rich alloys, and a reducing atmosphere affects a Type K pair Confirm the atmosphere at the point, because the temperature figure alone does not settle the choice

Questions Buyers Ask

What does MI stand for, and what is inside the cable?

Mineral insulated. The insulation is compacted magnesium oxide, the conductors are the thermocouple alloys, copper or a resistance alloy, and the outer layer is a drawn metal sheath in stainless steel or a nickel alloy. There is no polymer anywhere in the construction.

Is MI cable the same thing as a thermocouple cable?

No. Mineral insulated is a construction, and a thermocouple cable is one use of it. The same construction carries copper for power and a resistance alloy for heating, which is why the designation reads differently for each duty.

Does MI cable need a special termination?

Yes. The end has to be sealed against moisture, using the gland or pot seal that suits the sheath and the environment. The construction is what makes the cable survive fire and heat; the termination is what keeps it dry, and a poor one is the usual reason a sound cable fails in service.

Can MI cable be bent and cut like an ordinary cable?

It can be bent, but not to the radius a flexible cable allows, and it can be cut to length on site. The mineral insulation is compacted powder and not a solid, so a tight bend or a crushed sheath damages the insulation around the conductor even when the cable still looks intact from outside.

What causes an MI cable to fail in service?

Almost always moisture that reaches the magnesium oxide, through a termination that was not sealed or a sheath that was breached during installation. The second cause sits in the environment and not in the cable: a nickel-rich sheath in a sulfur-bearing gas, or an unprotected Type K pair in a reducing atmosphere, both fail earlier than the temperature rating suggests.

What sets the diameter to order?

Two things in opposition. A narrow sheath reaches the process temperature faster and takes up less room; a wider sheath survives more mechanical load and lasts longer in a hostile atmosphere. The diameter also caps the working temperature, because a thin sheath oxidises through sooner.

Summary

Mineral insulated cable is a construction, not a single product, and the name states it: a metal sheath, a compacted mineral insulator and a conductor chosen for the duty. What varies between orders is the conductor, the sheath and the diameter, and those three decide the temperature, the atmosphere the cable survives and how fast it responds.

DLX Alloy has produced nickel and nickel alloy products at Changzhou, Jiangsu since 2002, in a 12,000 m² factory certified to ISO 9001 with SGS audits. MI cable is supplied in the thermocouple types above with SS304, SS316, SS321 and Incoloy 800 sheaths, from 0.5 mm to 12.7 mm: send the duty, the atmosphere and the temperature for a confirmed quotation.

References

  1. IEC 60702-1 and BS EN 60702-1, the standard covering mineral insulated cables rated up to 750 V. Source for the construction described under the three parts.
  2. GB/T 13033, the Chinese standard for the same cable family and its terminations. Source for the designation fields.
  3. IEC 60331 and BS 6387, circuit integrity under fire, and resistance to fire with water and mechanical shock. Source for the fire behaviour, and for the comparison against fire-rated polymer cable.
  4. IEC 60584-1 and IEC 60584-3, thermocouple EMF tables and tolerances, and metal-sheathed mineral insulated extension cables. Source for the type designations.
  5. ASTM E230, temperature-EMF tables for standardized thermocouples. Source for the type ranges.
  6. Maximum operating temperature guide for mineral insulated thermocouple sheaths, TC Ltd. Source for the relationship between sheath material, diameter and working temperature.
  7. Product data held by DLX Alloy. Source for the designations, sheath materials and diameters listed on this page.

The figures quoted are nominal and are not acceptance limits. There is no single temperature range for mineral insulated cable: a Type K pair in an Inconel 600 sheath at 8.0 mm is rated to 1,150 °C, the same pair in a stainless sheath is rated lower, and both fall again as the diameter narrows. The working figure is the lowest of the three, and it is confirmed against the application on each enquiry and not read from one cell of a table.